Carlo Gavazzi |
www.DataSheet4U.com
Current and Voltage Controls
Current Transformer, 1-Phase AC
Type TAD 4, TAD 6
• Cable/bus-bar type current transformer
• DIN-rail, bus-bar and panel mounting facility
• TAD4: class 0.5, currents from 200 to 800 A
• TAD 6: class 0.5, currents from 400 to 2000 A
TAD4
TAD6
Product Description
Ordering Key
Cable/bus-bar type current ty. Rated primary currents from
transformer with DIN-rail/bus- 100 A to 2000 A.
bar and panel mounting facili-
Model
Primary current
Secondary current
TAD4 200A 5A
Type Selection
Model
TAD4: Cable diameter:
max. 32 mm
Bus-bar size:
32 x 16 mm
41 x 11 mm
Primary current
TAD6: Cable diameter:
Refer to Range Table
max. 52 mm
Bus-bar size:
55 x 22 mDmataSheet4U.com
65 x 20 mm
DataShee
Input Specifications
Operating frequency
Max. system voltage
Rated insulation level
Short-time current rating
Ith
Idyn
Extended current rating
Security factor (FS)
40 to 60 Hz
0.72 kV
3 kV / 1 min. @ 50 Hz
Typical 100 In / 1 s
2.5 Ith
The short-time thermal cur-
rent Ith is anyway limited by
the cable/bus-bar size
120%
≤5
Output Specifications
Rated secondary current
5 A standard
1 A on request
General Specifications
Standards
Housing
Mounting
Standard accessories
Special features
Cable diameters
TAD 4:
TAD 6:
Bus-bar size
TAD 4:
TAD 6:
According to IEC 60185
ABS, self-extinguishing:
UL 94 V-0
DIN-rail 46277/bus-bar
and panel mounting (brackets
supplied with the CT)
Screws + washers for
secondary terminals
Brackets for panel mounting
Screws for cable/bus-bar
mounting
Sealable terminal block cover
1 A secondary current
Double ratio obtained on the
secondary
Tropicalization
max. 32 mm
max. 52 mm
32 x 16 mm or
41 x11 mm
55 x 22 mm or
65 x 20 mm
DataSheet4U.com
Specifications are subject to change without notice (26.10.99)
DataSheet4 U .com
1
www.DataSheet4U.com
TAD 4, TAD 6
Range Table
TAD 4:
Rated
Primary
Current
Rated secondary current 1 A/5 A
Class 0.51)
Class 11)
Burden
Burden
TAD 6:
Rated
Primary
Current
Rated secondary current 1 A/5 A
Class 0.51) Class 11)
Burden
Burden
100 A
150 A
200 A
250 A
300 A
400 A
500 A
600 A
800 A
-
-
4 VA
6 VA
6 VA
10 VA
10 VA
10 VA
10 VA
3 VA
3 VA
-
-
-
-
-
-
-
400 A
500 A
600 A
800 A
1000 A
1200 A
1500 A
2000 A
6 VA
6 VA
10 VA
10 VA
20 VA
20 VA
30 VA
30 VA
12 VA
12 VA
20 VA
20 VA
40 VA
40 VA
60 VA
60 VA
1) The accuracy class is depending on the burden output. For the same rated primary current, the higher the burden the lower the
class (class down-grade).
Dimensions
et4U.com
DataSheet4U.com
TAD4
Wiring Diagram
Output (Secondary)
L
N
44
TAD6
Standard Accessories
- Sealable plastic cover for
terminal block
- Brackets for panel mount-
ing
44
DataSheet4U.com
2
DataSheet4 U .com
Specifications are subject to change without notice (26.10.99)
|