CHiNT |
NJBK9 Motor protection relay
1. General
NJBK9 series motor protection relay (hereinafter
referred to as “Pro-tecter”) is used for overload protection,
locked rotor protection, phase failure protection, three-phase
unbalance protection, grounding protection and PTC
temperature protection for AC electromotors of a frequency
of 50Hz with a rated insulation voltage of up to 690V and a
rated operating current of 1A-200A during long-term and
discontinuous operation.
This protector is provided with RS485 interface and 4-20mA
current loop transmitter interface for network communication
and performs remote monitor & control on the motor and
fault query through opper computer.
This protecter is usually used to combine with AC contactor.
Standards: IEC 60947-4-1
2. Type designation
N JBK 9 - □ □ □/□/□
Relay
Protection Relay
Control power supply voltage
(AC220V, AC380V, AC/DC100V~240V)
Rated current: 5, 10, 30, 50, 200
None: 4mA~20mA analog transformation
is not available
M: 4mA~20mA analog transmission
None: Communication interface is not available
T: RS485 communication interface
Enclosure grade: 50, 200
Design sequence No.
Motor protection relay
Company code
3. Operation conditions
3.1 Altitude: should not exceed 2000m;
3.2 Ambient tempeature: -5℃~+40℃, and the average
temperature in 24h should not exceed +35℃;
3.3 Atmospheric conditions: The relative air humidity should not
exceed 50% at the maximum temperature of +40℃. The
relative humidity may be higher at lower temperatures, for
example, the air humidity can be up to 90% at +20℃. Special
measures should be taken if condensation occurs on the product
occasionally due to temperature variation;
3.4 Pollution degree: 3;
3.5 The inclination between the mounting plane and the vertical
plane should not exceed ±5°;
3.6 In non-explosive media that do not contain a sufficient
amount of gas or conductive dust to cause metal corrosion or
insulation failure;
3.7 In places with rain and snow protection equipment and not
full of vapor;
3.8 In places where there is no significant shake, impact or
vibration;
3.9 Mounting category: Ⅲ;
3.10 Degree of protection of enclosure: IP20.
I-23
> >>
Relay
Protection Relay
4. Technical data
4.1 Main circuit: rated insulation voltage: AC690V, rated frequency: 50Hz
Model
NJBK9-50□□/5/□
NJBK9-50□□/10/□
NJBK9-50□□/30/□
NJBK9-50□□/50/□
NJBK9-50□□/200/□
Setting current (A)
5
10
30
50
200
Setting current range (A)
1~5
2~10
6~30
10~50
40~200
Matching motor power (kW)
0.5~2.5
1~5
3~15
5~25
20~100
4.2 Auxiliary circuit: rated insulation voltage: AC380V, rated frequency: 50Hz, data of auxiliary contact
Usage category
Rated operational voltage Ue(V)
Rated operational current Ie(A)
Conventional heating current Ith(A)
AC-15
240
1.5
5
380
0.95
4.3 Product selection table
Model
NJBK9-50/□/□
NJBK9-50T/□/□
NJBK9-50M/□/□
NJBK9-50TM/□/□
NJBK9-200/□/□
NJBK9-200T/□/□
NJBK9-200M/□/□
NJBK9-200TM/□/□
Overload
◆
◆
◆
◆
◆
◆
◆
◆
Phase failure
◆
◆
◆
◆
◆
◆
◆
◆
Ground
◆
◆
◆
◆
◆
◆
◆
◆
PTC
◆
◆
◆
◆
◆
◆
◆
◆
Communication
◆
◆
◆
◆
4mA~20mA
◆
◆
◆
◆
Unbalance
◆
◆
◆
◆
◆
◆
◆
◆
Locked
rotor
◆
◆
◆
◆
◆
◆
◆
◆
4.4 Structural features
4.4.1 Split mounting;
4.4.2 LCD display, key setting;
4.4.3 Has start delay function;
4.4.4 Has fault memory function, permits inquiry of fault record;
4.4.5 Has RS485 interface, supports MODBUS protocol, permits network communication;
4.4.6 With 4mA-20mA analog output interface;
4.4.7 Has two groups of output contacts, 1Z protection contact and 1H auxiliary contact, and permits autotransformer reduced voltage
starting and star-delta starting;
4.4.8 Power consumption: ≤3VA.
5. Protection charactersitics
5.1 Operating characteristics of overload protection
Overload
curve
Kr=1
Kr=2
Kr=3
Kr=4
Kr=5
Overload multiple
Operation
time (s)
1.1 1.2 1.5
2
5
6 7.2
75 63 40 22 3.6 2.5 1.8
150 125 80 45 7.2 5 3.5
298 250 160 90 14 10 6.9
595 500 320 180 29 20 14
892 750 480 270 43 30 21
Note
In conformity with Class 10A
In conformity with Class 10
In conformity with Class 20
In conformity with Class 30
I