LEM |
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
I = 10 .. 400 A
PN
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
Analogue Output Signal
VOUT (V)
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
Type
AP 50 B10
AP 100 B10
AP 200 B10
AP 400 B10
R Load resistance
L
≥ 10 kΩ
VC Supply voltage
+24 ±5% V DC
Vd R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5 kV
Limitation voltage output
18 V
Accuracy-Dynamic performance data
X
εL
VOE
εVOT
TC G
t
r
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of I
P
Frequency bandwidth (-3 dB)
< ±1
< ±0.5
< ±0.5
±1
% of IPN
% of IPN
% of IPN
mV/K
±0.1 %/K
< 500
ms
10 .. 6000 Hz
General data
T Ambient operating temperature
A
T Ambient storage temperature
S
m Mass
-20 .. +60
-20 .. +85
90
°C
°C
g
Protection type
IP20
Reliable isolation according to EN50178, EN61010 300
V AC
Creepage distance
> 5.5
mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Features
• RMS output
• Split core type
• 5V & 10V switch selectable voltage
output.
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
• Panelmeters
Simple connection displays power
consumption.
Notes : Installation and maintenance should be done with power supply disconnected.
LEM Components
030708/0
www.lem.com
Dimensions AP(R)-B10 (unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
• General tolerance
±1 mm
• Primary aperture
∅ 18.5 mm
• Panel mounting
2 holes ∅ 4.0 mm
• Distance between holes
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
0-5, 10V Selec table
A P /A P R
GND
RL
OUTPUT
+2 4 V D C
O u tp u t
C o n n e c to r
3 (-) 2 (out)1 (+)
O u tp u t S w itc h
R a n g e S w itc h
F ront
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
|