Bussmann |
Bussmann®
Transient Voltage Surge Suppression Limiters TVSS
General Information:
• Designed to protect TVSS systems per UL 1449 Second
Edition Requirements.
• Able to withstand 8x20 µSec surge pulses without opening.
• Limiters are identified by a surge rating and not continuous
current rating.
Dimensional Data
TVSS-( )
Catalog Symbol: TVSS
Physical Size: Refer to “Dimensional Data”
Construction:
Melamine Tube
Nickel Plated Brass End Caps
Voltage Rating: 600Vac
Interrupting Rating:
200,000A RMS Sym.
Agency Approvals:
UL Recognized 600Vac, File E56412
Catalog Symbol and Surge Ratings
CATALOG
8x20µS
MELTING I2t CLEARING I2t
NUMBER SURGE RATING
(A2s)
(A2s)
TVSS-5
5,000A
559 1,650
TVSS-10
10,000A
1,788
5,766
TVSS-15
15,000A
3,760
9,730
TVSS-20
20,000A
6,020
14.000
Ipeak @ 100kA
60 Hz (A)
4,283
6,618
7,843
8.594
Above catalog numbers are available with Printed Circuit Board Tabs. When
ordering, use suffix “-01”.
TVSS-( )-01
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
9-01-04
SB04303
Recommended fuseblocks/fuseholders for
13/32” x 1-1/2” fuses
See Data Sheets listed below
• Open fuseblocks - 1104, 2104
• Finger-safe fuseholders - 1109, 1102, 1103, 1151
• Panel-mount fuseholders - 2114, 2113, 2108,
• In-line fuseholders - 2127, 2126
Form No. TVSS
Page 1 of 3
Data Sheet: 2141
Bussmann®
Transient Voltage Surge Suppression Limiters TVSS
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
300
200
100
10
1
.1
.01
CURRENT IN AMPERES
9-01-04
SB04303
Form No. TVSS
Page 2 of 3
Data Sheet: 2141
|