Omron |
Single-phase Voltage Relay
K8AB-VS
Ideal for voltage monitoring for industrial
facilities and equipment.
• Monitor for overvoltages or undervoltages.
• Manual resetting and automatically resetting supported by one
Relay.
• One SPDT output relay, 6 A at 250 VAC (resistive load).
• Output relay can be switched between normally open and
normally closed.
• Process control signal (0 to 10 V) and current splitter input
supported.
• Output status can be monitored using LED indicator.
• Input frequency of 40 to 500 Hz supported.
• Inputs are isolated from the power supply.
Refer to Safety Precautions for the K8AB
Series. Refer to page 9 for the Q&A section.
Model Number Structure
■ Model Number Legend
K8AB-@@
1 23
4
1. Basic Model
K8AB:
Measuring and Monitoring Relays
2. Functions
VS: Single-phase Voltage Relay (One-sided operation)
3. Measuring Current
1: 6 to 60 mV AC/DC, 10 to 100 mV AC/DC, 30 to 300 mV AC/DC
2: 1 to 10 V AC/DC, 3 to 30 V AC/DC, 15 to 150 V AC/DC
3: 20 to 200 V AC/DC, 30 to 300 V AC/DC, 60 to 600 V AC/DC
4. Supply Voltage
24 VAC/DC: 24 VAC/DC
100-115 VAC: 100 to 115 VAC
200-230 VAC: 200 to 230 VAC
CSM_K8AB-VS_DS_E_3_1
www.DataSheet4U.com
1
Ordering Information
K8AB-VS
■ List of Models
Single-phase Voltage Relay
Measuring voltage
6 to 60 mV AC/DC,
10 to 100 mV AC/DC,
30 to 300 mV AC/DC
1 to 10 V AC/DC,
3 to 30 V AC/DC,
15 to 150 V AC/DC
20 to 200 V AC/DC,
30 to 300 V AC/DC,
60 to 600 V AC/DC
Supply voltage
24 VAC/DC
100-115 VAC
200-230 VAC
24 VAC/DC
100-115 VAC
200-230 VAC
24 VAC/DC
100-115 VAC
200-230 VAC
Model
K8AB-VS1 24 VAC/DC
K8AB-VS1 100-115 VAC
K8AB-VS1 200-230 VAC
K8AB-VS2 24 VAC/DC
K8AB-VS2 100-115 VAC
K8AB-VS2 200-230 VAC
K8AB-VS3 24 VAC/DC
K8AB-VS3 100-115 VAC
K8AB-VS3 200-230 VAC
■ Shunts (Order Separately)
A shunt is a resistor to convert a DC current into a DC voltage.
Use the shunt in combination with K8AB-VS to detect undercurrent and overcurrent in DC circuits.
Model
SDV-SH5
SDV-SH7.5
SDV-SH10
SDV-SH15
SDV-SH20
SDV-SH30
SDV-SH50
SDV-SH75
SDV-SH100
SDV-SH150
SDV-SH200
SDV-SH300
SDV-SH500
SDV-SH750
SDV-SH1000
Rated current
5A
7.5 A
7.5 A (for 100 mV)
10 A
15 A
20 A
30 A
50 A
75 A
100 A
150 A
200 A
300 A
500 A
750 A
1,000 A
Output voltage
60 mV
100 mV
60 mV
Ratings and Specifications
Characteristics
SDV-SH5 (Rated Current: 5 A)
Shunt rated
at 60 mV
60
5 Input current (A)
Note: 1. All the above listed shunts have an accuracy in the 1.0 class.
2. Select a shunt whose rated current is more than 120% of the
current normally flowing in a circuit. The characteristics of the
shunt may change or fusing of a resistor element may occur if an
overload that is 1,000% of the rated current is applied. Therefore,
determine the rated current of the shunt to be used, by taking the
circuit conditions into account.
■ Input Range
Model
K8AB-VS1
K8AB-VS2
K8AB-VS3
Range*
0 to 60 mV AC/DC
0 to 100 mV AC/DC
0 to 300 mV AC/DC
0 to 10 V AC/DC
0 to 30 V AC/DC
0 to 150 V AC/DC
0 to 200 V AC/DC
www.DataSheet40Ut.oco3m00 V AC/DC
0 to 600 V AC/DC
Connection terminal
V1-COM
V2-COM
V3-COM
V1-COM
V2-COM
V3-COM
V1-COM
V2-COM
V3-COM
Measuring voltage
6 to 60 mV AC/DC,
10 to 100 mV AC/DC,
30 to 300 mV AC/DC
1 to 10 V AC/DC,
3 to 30 V AC/DC,
15 to 150 V AC/DC
20 to 200 V AC/DC,
30 to 300 V AC/DC,
60 to 600 V AC/DC
Input impedance
Approx. 220 kΩ
Approx. 230 kΩ
Approx. 260 kΩ
Approx. 120 kΩ
Approx. 320 kΩ
Approx. 1.6 MΩ
Approx. 1.2 MΩ
Approx. 1.7 MΩ
Approx. 3.1 MΩ
Overload capacity
Continuous input:
115% of maximum input
10 s max.:
125% of maximum input
* The range is selected using connected terminals.
2
|