EPCOS |
4-Line Filters
for Installations and Systems
Power line filters for three-phase systems
with additional VHF suppression
Rated voltage 440/250 V~, 50/60 Hz
Rated current 6 to 75 A
Construction
s Four-line filter
s Metal case
s Screw-type cable fitting for strain relief
on line side, edge protector on load side
s Feed-through capacitors
Features
q High insertion loss up to the GHz range
Applications
q Power supplies for industrial installations
q Medical engineering
s Packaging machines
www.DataSheet4TUe.cromminals
s Safe-to-touch terminal clamps incorporated in case
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
B84299-K33
… B84299-K39
304 03/01
4-Line Filters
for Installations and Systems
Circuit diagram
B84299-K33
… B84299-K39
L1
L2
LNINetEz
L3
N
L1’
L2’
LLaOstAD
L3’
N’
Typical circuit taking the example of B84299-K35
SSB0543-U
Technical data
Rated voltage VR
Rated current IR
Test voltage VP
Leakage current l leak
Climatic category
440/250 V~, 50/60 Hz
referred to 40 °C ambient temperature
1414 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
at 400 V~, 50 Hz
in accordance with EN 60068-1
40/085/21 (– 40 °C/+ 85 °C/21 days damp heat test)
Characteristics and ordering codes
IR
l leak
Terminal
Approx.
cross section weight
A
mA mm2
kg
6
<5
4
16
<5
4
25
<5
4
50
<5
16
75
< 10
25
1,8
2,1
3
7,5
11
Ordering code
B84299-K33
B84299-K35
B84299-K36
B84299-K37
B84299-K39
Approvals
×
× (for 14 A)
× (for 20 A)
× (for 40 A)
× (for 65 A)