파트넘버.co.kr MP1402 데이터시트 PDF


MP1402 반도체 회로 부품 판매점

(MP1400 - MP1423) RTD Input Limit Alarm



M-System 로고
M-System
MP1402 데이터시트, 핀배열, 회로
INSTRUCTION MANUAL
RTD INPUT LIMIT ALARM
model
MP1400 through MP1423
Thank you for choosing M-System. Before use, check specifications
on the unit label.
If you have any problems or questions with the product, please contact
M-System’s Sales Office or representatives.
General Description
The M-PAC Model MP1400 through MP1423 accept 2- or 3-wire RTD
inputs and provide relay contact closure(s) at a preset input level. The
MP1400 Series reflects three styles of output selection:
MP1400 – MP1403 Single (Hi) trip, non-latching (DPDT, 3A)
MP1410 – MP1413 Single (Hi) trip, latching (DPDT, 3A)
MP1420 – MP1423 Dual (Hi/Lo) trip, non-latching (SPDT, 3A)
•Upscale burnout protection as standard
•Failsafe operation available
www.Dat••aDInSedaihcdaebtaoenrtdL4EaUDdj.upcsrootavmbidleedfrom 1 to 100%
Installation [Scale: mm(inch)]
•Operating temperature: -5 to +60°C (23 to 140°F)
•Operating humidity: 30 to 90% RH (non-condensing)
Keep away from water, corrosive gas, dust and vibration. DIN rail
mounting available for 11-pin-base modules. Use DIN rail of 35 mm
width.
•11-Pin Base
55 (2.17) min.
40 ± 0.2
40 ± 0.2 2–M4 SCREW
(1.57± .01) (1.57± .01)
Adjustments
•Setpoint The MP1400 Series has five styles of setpoint adjustment:
MP14X0 Top-accessed, 3-turn screw(s)
MP14X2 Remote dial connection(s), 1k to 100k ohms
MP14X3 DC-programmable, 0 to 1V
The setpoint is adjustable over the entire input span.
A) Set deadband at its minimum (fully counterclockwise) before ad-
justing the setpoint.
B) With the specified trip Resistance/RTD input applied, adjust setpoint
until the relay trips. For Hi trip calibration, start with the setpoint
above the desired trip. For Lo trip calibration start below the desired
trip.
•Deadband The deadband is independently adjustable for both
setpoints in dual alarms.
A) Set deadband at its minimum (fully counterclockwise). Set setpoint
to desired trip.
B) Adjust Resistance/RTD input until relay trips.
C) Re-adjust deadband to 100% (fully clockwise).
D) Set Resistance/RTD input to desired deadband position.
E) Slowly adjust deadband until relay untrips.
•Transmitter Output (Option T)
A) With the specified minimum input applied, adjust Zero for 0.00V at
the transmitter output.
B) With the specified maximum input applied, adjust Span for 1.00V.
Repeat A) to B) for best accuracy.
Relay Protection
•Output Relay Rating 30V DC @3A (resistive load) or
120V AC @3A (cosø=1)
For maximum relay life with inductive loads, external protection is
recommended. Refer to the Figures below.
•20-Pin Base
85 (3.35) min.
56 ± 0.2
(2.20 ±0.01)
56 ± 0.2
(2.20 ±0.01)
2–M4 SCREW
•DC Line Powered Loop Place a diode across the load.
DC Power
Limit Alarm
LOAD
•AC Line Powered Loop Place a varistor or CR spark killer across
the load.
AC Power
Terminal Connections
Make wiring to terminals as shown in the Tables in Page 2 through 3.
Use the socket provided with the module.
Limit Alarm
LOAD
Spark Quenching
Circuit
P. 1 / 3 EM-9804 Rev.3


MP1402 데이터시트, 핀배열, 회로
External Dimensions [Scale: mm(inch)]
•11-Pin Base
50 (1.97)
www.Data20S-PhieneBta4sUe .com
103 (4.06)
132 (5.20)
MP1400 through MP1423
CLAMP
(top & bottom)
DIN RAIL
35mm wide
7.8 (.31)
87
65
4
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
[3.3 (.13)]
9
10 11
3
12
40 (1.57)
50 (1.97)
8 (.31)
2–M3 SCREW
(for module)
975431
86
2 20
80 (3.15)
103 (4.06)
136 (5.35)
33 (1.30)
2–4.5 (.18) dia.
MTG HOLE
20–M3.5
SCREW
10 12
16 18
11 13 14 15 17 19
56 (2.20)
71 (2.80)
Terminal Assignment
•Single Output
MP1400
1 POWER (Hot/+)
2 RTD Comp Lead
3 POWER (Neu/–)
4 RTD Hi
5 RTD Lo
6 N.O.
7 COM *
8 N.C. *
9 N.O.
10 COM
11 N.C.
MP1400
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 No Connection
6 No Connection
7 No Connection
8 SP Xmtr +
9 RTD Lo
10 Xmtr Common
11 RTD Hi
12 Proc Xmtr +
13 N.O.
14 COM *
15 N.C. *
16 No Connection
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1402
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 SP Pot CCW
6 SP Pot W
7 SP Pot CW
8 No Connection
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *
15 N.C. *
16 No Connection
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1402
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 SP Pot CCW
6 SP Pot W
7 SP Pot CW
8 SP Xmtr +
9 RTD Lo
10 Xmtr Common
11 RTD Hi
12 Proc Xmtr +
13 N.O.
14 COM *
15 N.C. *
16 No Connection
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1403
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 SP –
6 SP +
7 No Connection
8 No Connection
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *
15 N.C. *
16 No Connection
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1403
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 SP –
6 SP +
7 No Connection
8 SP Xmtr +
9 RTD Lo
10 Xmtr Common
11 RTD Hi
12 Proc Xmtr +
13 N.O.
14 COM *
15 N.C. *
16 No Connection
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
KEYS
N.O. = Normally Open
COM = Common
N.C. = Normally Closed
Proc = Process
Xmtr = Transmitter
SP = Setpoint
W = Wiper
CW = Clockwise
CCW =
␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ Counterclockwise
*Pins used for
Option V
20-pin = 14(+) - 15(–)
11-pin = 7(+) - 8(–)
P. 2 / 3 EM-9804 Rev.3




PDF 파일 내의 페이지 : 총 3 페이지

제조업체: M-System

( m-system )

MP1402 data

데이터시트 다운로드
:

[ MP1402.PDF ]

[ MP1402 다른 제조사 검색 ]




국내 전력반도체 판매점


상호 : 아이지 인터내셔날

전화번호 : 051-319-2877

[ 홈페이지 ]

IGBT, TR 모듈, SCR, 다이오드모듈, 각종 전력 휴즈

( IYXS, Powerex, Toshiba, Fuji, Bussmann, Eaton )

전력반도체 문의 : 010-3582-2743



일반적인 전자부품 판매점


디바이스마트

IC114

엘레파츠

ICbanQ

Mouser Electronics

DigiKey Electronics

Element14


관련 데이터시트


MP1400

(MP1400 - MP1423) RTD Input Limit Alarm - M-System



MP1402

(MP1400 - MP1423) RTD Input Limit Alarm - M-System



MP1403

(MP1400 - MP1423) RTD Input Limit Alarm - M-System



MP140x

(MP1400 - MP1423) RTD Input Limit Alarm - M-System