Magnetic Hydraulic
Circuit Breakers
Features
• Designed for the international market. UL Recognized, CSA Certified,
and VDE approved.
• Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
• Optional 10 amp auxiliary switch.
• Optional snap-in mounting. (W6)
• Several delay curve options.
• Trip-free operation.
Agency Approvals
UL: Recognized as Supplementary Protector under UL 1077. File
E69543.
CSA: Certified as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782.
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details.
Calibration: Breakers will hold 100% of rated current. Breakers may trip
between 101% and 124% of rated load (149% for 400 Hz.
units and 134% for AC/DC units). Breakers must trip at
125% of rated load and above (150% for 400 Hz. units and
135% for AC/DC units).
Dielectric Strength: 50/60 or 400 Hz., 1500V: DC, 1100V.
Insulation Resistance: 100 Megohms at 500VDC.
Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Approvals and Ratings Table 1
W6 Series
UL/CSA (All Circuit Functions)
Maximum
Voltage
65
277
277
277/480
250
250
250
Frequency
(Hz)
DC
50/60
50/60
50/60
400
400
400
Current
Phase
-
1
1
3Ø-Wye
1
1
3Ø-Wye
Interrupting
Rating
(Amps)
0.2 - 50
0.2 - 20
21 - 50
0.2 - 20
0.2 - 20
21 - 50
0.2 - 20
W9 Series
Maximum
Voltage
65
277
277/480
250
250
UL/CSA (All Circuit Functions)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
400
400
-
1
3Ø-Wye
1
3Ø-Wye
0.2 - 50
0.2 - 50
0.2 - 20
0.2 - 50
0.2 - 50
Capacity
(Amps)
2,000
5,000
2,500
5,000
2,500
1,250
2,500
Capacity
(Amps)
2,000
5,000
5,000
2,500
2,500
Approvals and Ratings Table 2
UL/CSA
Switch
Number
A
Voltage
50/60 Hz.
125
Current
(Amps)
10
Terminals
WxTxL
.093 x .020 x .250
(2.36 x .51 x 6.40)
Typical Resistance and Impedance
DC 50/60 Hz.
Current
Resistance
Impedance
(Amps)
(Ohms)
(Ohms)
0.2 90
90
1.0 1.2
1.2
2.0 0.28 0.28
5.0 0.04 0.04
10.0
0.013
0.013
20.0
0.004
0.005
30.0
0.0027
0.004
40.0
0.002
0.002
50.0
0.0015
0.0015
400 Hz.
Impedance
(Ohms)
180
2.0
0.50
0.05
0.025
0.0065
0.004
0.003
0.0025
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms).
Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm)
total excursion in 2 planes.
Fungus And Moisture Resistance: Special moisture resistant finish
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Marking: W6 units have ON and OFF molded on the rocker of rocker
actuated units (rocker actuated VDE units have international
“1” and “0”). W9 units have ON and OFF molded into the area
at the base of the toggle. International “1” and “0” symbols are
marked on the toggle for both W6 and W9.
Mounting: Panel mounted units are mounted with two #6-32 screws
from the front of the panel. Metric models for use with M3 x
0.5 screws are available. Units with snap-in mounting option
snap through the front of the panel. To maintain published
performance specifications, units should not be mounted
more than 90° from their normal upright position.
Weight: Approximately 2.5 ounces per pole.
W6 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
W9 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
VDE
Switch
Number
V1
V2
V3
Voltage
50/60 Hz.
250
250
250
Current
(Amps)
10
5
0.1
Terminals
WxTxL
.110 x .020 x .280
(2.79 x .51 x 7.11)


W91-X112-50 데이터시트, 핀배열, 회로
Time vs. Current Trip Curves For W6 Series and W9 Series
AC 50/60 Hz.
400 Hz.
10,000
1000
100
10
1
DC & 50/60 Hz.
CURVE 0 NON-TIME DELAY
TRIP TIMES
OVERLOAD @ 50/60 Hz. & DC @ 400 Hz.
125%
150%
200%
400%
600%
800%
100 ms max.
55 ms max.
30 ms max.
15 ms max.
12 ms max.
12 ms max.
May Trip
100 ms max.
30 ms max.
15 ms max.
12 ms max.
12 ms max.
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
1
CURVE 2 AC VOLTAGE 50/60 Hz.
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
10 - 150
2.2 - 20
.2 - 2
.03 - .75
.007 - .15
.005 - .04
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
1
CURVE 3 AC VOLTAGE 50/60 Hz.
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
1 - 15
.15 - 1.5
.03 - .25
.007 - .15
.003 - .08
.003 - .04
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
MOTOR START
CURVE 10 HIGH INRUSH 50/60 Hz. AC
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
40 - 500
9 - 100
2 - 20
.8 - 10
.1 - 4.5
.009 - 2
1
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
DC
10,000
1000
100
10
1
CURVE 2 DC VOLTAGE
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
2 - 55
.60 - 8
.1 - 1.5
.02 - .5
.004 - .05
.004 - .025
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
1
CURVE 12 HIGH INRUSH 50/60 Hz.
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
10 - 150
3 - 25
.5 - 2.5
.15 - 1
.015 - .7
.009 - .35
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
1
CURVE 3 DC VOLTAGE
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
.6 - 7
.16 - 1.5
.03 - .25
.01 - .13
.004 - .05
.003 - .015
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
1
CURVE 13 HIGH INRUSH 50/60 Hz.
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
.8 - 30
.15 - 2.5
.03 - .3
.02 - .15
.009 - .12
.009 - .09
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
10,000
1000
100
10
CURVE 53 DC HIGH INRUSH
OVERLOAD TRIPTIMES
(SEC.)
125%
200%
400%
600%
800%
1000%
80 - 700
15 - 150
2 - 20
.70 - 10
.10 - 3
.01 - .1
1
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
AC/DC
AC 400 Hz.
10,000
1000
100
10
1
CURVE 34 DC, 50/60 Hz. STANDARD DELAY
OVERLOAD TRIPTIMES
(SEC.)
135%
200%
400%
600%
800%
1000%
1 - 90
.60 - 20
.095 - 2
.02 - .95
.002 - .45
.002 - .09
10,000
1000
100
10
1
CURVE 2 AC VOLTAGE 400 Hz.
OVERLOAD TRIPTIMES
(SEC.)
150%
200%
400%
600%
800%
1000%
5 - 60
2.2 - 20
.3 - 3.2
.01 - .17
.006 - .06
.005 - .045
.1 .1
.01 .01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
135 OF BREAKER RATING
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
Note:
For instantaneous curves for all voltages refer to Curve 0 Non-Time Delay under the AC 50/60 Hz. heading.
Pulse Tolerance Specifications
Pulse tolerance is defined as a single pulse of a half sine
wave (1/2 cycle or 8 milliseconds) that will not trip the
breaker. An inertia wheel for increased pulse tolerance is
available by specifying “P” after the time delay curve
number in the ordering information. The table at right lists
pulse tolerance values of standard and inertia delay models.
Voltage
AC
50/60 Hz.
AC
400 Hz.
Time
Delay
Curve
2
3
10
12
13
2
3
10,000
1000
100
10
1
CURVE 3 AC VOLTAGE 400 Hz.
OVERLOAD TRIPTIMES
(SEC.)
150%
200%
400%
600%
800%
1000%
.55 - 5.5
.18 - 2
.02 - .2
.006 - .075
.004 - .05
.004 - .035
.1
.01
.001
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
125 150
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
Pulse Tolerance Value
Standard
Inertia
Delay
7.5 18
6 18
18 30
18 30
18 30
6.5 18
5.5 18
To determine pulse tolerance multiply breaker rating by value in table. For
example, a 2A breaker with time delay curve 3 has a standard pulse tolerance
of 12A (2A x 6). The same breaker with an inertia delay has a pulse tolerance
of 36A (2A x 18).




PDF 파일 내의 페이지 : 총 6 페이지

제조업체: Tyco

( tyco )

W91-X112-50 data

데이터시트 다운로드
:

[ W91-X112-50.PDF ]

[ W91-X112-50 다른 제조사 검색 ]




국내 전력반도체 판매점


상호 : 아이지 인터내셔날

전화번호 : 051-319-2877

[ 홈페이지 ]

IGBT, TR 모듈, SCR, 다이오드모듈, 각종 전력 휴즈

( IYXS, Powerex, Toshiba, Fuji, Bussmann, Eaton )

전력반도체 문의 : 010-3582-2743



일반적인 전자부품 판매점


디바이스마트

IC114

엘레파츠

ICbanQ

Mouser Electronics

DigiKey Electronics

Element14


관련 데이터시트


W91-X112-5

Magnetic Hydraulic Circuit Breakers - Tyco



W91-X112-50

Magnetic Hydraulic Circuit Breakers - Tyco