MTU Onsite Energy |
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
1000-XC6DT2
1000 ekW / 60 Hz / Standby
900 ekW / 60 Hz / Prime
208 - 4160V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
wwwGTee.mDnepartRaatiSsoher eMeot4deUl*.c om
Connection
208V**
3
0.8
60
1000
1250
3470
2600
741RSL4045
130°C/27°C
12 LEAD LOW WYE
208V
3
0.8
60
900
1125
3123
2600
741RSL4045
105°C/40°C
12 LEAD LOW WYE
240V**
3
0.8
60
1000
1250
3007
2600
741RSL4045
130°C/27°C
12 LEAD HI DELTA
240V
3
0.8
60
900
1125
2706
2600
741RSL4045
105°C/40°C
12 LEAD HI DELTA
480V**
3
0.8
60
1000
1250
1504
2600
575RSL4044
130°C/27°C
4 BAR WYE
480V
3
0.8
60
900
1125
1353
2600
575RSL4044
105°C/40°C
4 BAR WYE
600V**
3
0.8
60
1000
1250
1203
1550
741RSS4282
125°C/40°C
4 LEAD WYE
600V
3
0.8
60
900
1125
1083
1550
741RSS4282
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
4160V
3
0.8
60
1000
1250
173
2600
742FSM4364
130°C/27°C
6 LEAD WYE
4160V
3
0.8
60
900
1125
156
2600
742FSM4364
105°C/40°C
6 LEAD WYE
2 / // / 1000-XC6DT2
Facts
// EPA Tier 2 Certified
// Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
// UL2200, CSA Listing Offered
// Accepts Rated Load in One Step Per NFPA 110, Level 1
// All engine-generator sets are prototype and factory tested
// MTU Onsite Energy is a single source supplier
// Global Product Support
// 2 Year Standard Warranty
// Custom Design for Any Application
// 16V-2000 G84 Diesel Engine
- 31.8 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
STANDARD EQUIPMENT
// Complete Range of Accessories
// Permanent Magnet Generator (PMG)
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
// Digital Control Panel(s)
- UL Recognized, , NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// Engine
Air Cleaners
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Inter Cooler Water Pump
Closed Crankcase Vent
Thermostats
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electric Isochronous
Base - Structural Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
awndwmwo.tDorasttaaSrhtineget4U.com
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±.25% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
|