Temperature Controller
A 96 x 96 mm (DIN) Controller for
Control Valves
Controls motor valves without a potentiometer.
Optimum PID control with feed-forward control
circuitry.
High precision regardless of the set temperature.
Compatible with various inputs (input selected via
internal switch).
Models with communications capabilities also
available.
E5AX-P
Ordering Information
Electronic Temperature Controller
Communica-
tions
None
RS-232C
RS-422*
RS-485*
BCD
Transmission
output*/**
(4 to 20 mA)
Communications
Board Add-on Type
Model
E5AX-PRR E5AX-PRR01 E5AX-PRR02 E5AX-PRR03 E5AX-PRR20 E5AX-PRRF
E5AX-PRRM
*The Controller can also be equipped with a terminal block to connect communications. Specify a terminal block by adding “-X” to the model
number. Example: E5AX-PRR02-X
**Capable of transmitting the process value or output value, but remote setting by external input is not possible.
Temperature Ranges
Input (switch
selectable)
Thermocouple
Temperature
resistance
thermometer
K
Chromel vs.
alumel
J/L
Iron vs.
constantan
T/U
Copper vs.
constantan
E
Chromel
vs.
constantan
R
Platinum vs.
platinum
13% rhodium
S
Platinum vs.
platinum 10%
rhodium
PT platinum
resistance
thermometer
(Pt100/JPt100)
Range %C –200 to 1,300 –100 to 850 –200 to 400 0 to 600
%F –300 to 2,300 –100 to 1,500 –300 to 700 0 to 1,100
Resolution (%C/%F) 1
(main settings and
alarm)
Communications Boards
omCommunications
RS-232C
www.datasheet4u.cModel
E53-X01
RS-422
E53-X02
RS-485
E53-X03
0 to 1,700
0 to 3,000
0 to 1,700
0 to 3,000
–99.9 to 450.0
–99.9 to 800.0
0.1
BCD
E53-X20
Transmission output
(4 to 20 mA)
E53-XF
1

1 page




E5AX-P pdf
E5AX-P
E5AX-P
sible settings for temperature sensors. Refer to temperature range
charts under Ordering Information for further information.
The scale displayed (%C or %F) is selected by the operating mode
selector (SW201).
Operating Mode Selector (SW201,
FUNCTION)
This DIP switch selects the operation modes listed in the following
table.
Function
Pin Pin
number setting
Control setting
Not used.*
1 Leave turned OFF.
Control output
2
ON Normal (cooling)
Switch
setting
0
1
2
3
4
5
6
7
Temperature
sensor code
Temperature range
%C %F
R
0 to 1,700
0 to 3,000
S
0 to 1,700
0 to 3,000
K –200 to 1,300 –300 to 2,300
J –100 to 850 –100 to 1,500
T –200 to 400 –300 to 700
E
0 to 600
0 to 1,100
JPt100
–99.9 to 450.0 –99.9 to 800.0
Pt100
–99.9 to 450.0 –99.9 to 800.0
OFF Reverse (heating)
Input shift
3 ON Enabled
OFF Disabled
SP (set point)**
4
ON Enabled
protection cancel
OFF Disabled
Display unit 5 ON %F
OFF %C
PID display
6 ON Enabled
OFF Disabled
*Always operate with pin 1 OFF. Operating with pin 1 ON could re-
sult in malfunction.
8L
9U
–100 to 850
–200 to 400
–100 to 1,500
–300 to 700
**SP protection cancel is effective only when SW101 (key protec-
tion) is on. If the SP protection cancel is ON, key protection (SW101
ON) will not apply to the set point, i.e., you will be able to change the
set point regardless of the setting of SW101.
Alarm Mode Selector (SW205: ALM)
Alarm mode selector is provided on all E5AX Temperature Controllers. Alarm modes, listed in the following table, can be selected using this
switch. The switch is factory-set to position 2, i.e., the upper-limit alarm mode.
Switch
Mode (SW205)
Alarm output
Setting range
setting Alarm operation
Display When X is positive
When X is negative
0 No alarm
No display OFF
---
1 Upper- and lower-limit )––(
alarm
XX
---
Thermocouple: 0% to
9,999%C/%F
Platinum resistance thermometer:
0% to 999.9%C/%F
2
Upper-limit alarm
–––(
X X Thermocouple: –999% to
9,999%C/%F
3
Lower-limit alarm
)–––
X
X Platinum resistance thermome-
ter: –99.9% to 999.9%C/%F
4 Upper- and lower-limit –()–
range alarm
XX
---
Thermocouple: 0% to
9,999%C/%F
5 Upper- and lower-limit 3––e
alarm with standby se-
quence
6 Upper-limit alarm with –––e
standby sequence
XX
X
---
X
Platinum resistance thermometer:
0% to 999.9%C/%F
Thermocouple: –999% to
9,999%C/%F
7 Lower-limit alarm with 3–––
standby sequence
X
X Platinum resistance thermome-
ter: –99.9% to 999.9%C/%F
8 Absolute-value alarm 1––(
Y
0%C
Y
0%C
5

5 Page





E5AX-P arduino
E5AX-P
E5AX-P
Starting Control Operation
The E5AX will start control operations as soon as power is turned on
until power is turned off. If you don’t want control operations to be
performed while setting parameters, turn off the power and then turn
it back on after setting the desired parameters.
Main setting
Previous PID
constants
New PID constants
Auto-tuning
When the Level Key and Mode Key are pressed at the same time for
1 second minimum, the Temperature Controller automatically starts
tuning the PID constants. While auto-tuning is in operation, the au-
to-tuning indicator on the front panel will flash. The Temperature
Controller executes control based on the set PID constants (factory
set to P = 40%C, I = 240 seconds, and D = 40 seconds) until the tem-
perature of the controlled system reaches the set temperature. After
that, the Temperature Controller automatically adjusts the PID con-
stants using the limit cycle method. When the auto-tuning indicator
turns off, the auto-tuning is terminated and PID constants are re-
newed.
Error Messages
AT indicator flashes
Limit Cycle Method: the optimum PID constants are calculated by
this method by varing the control output variable and generating ex-
ternal oscillation.
Auto-tuning can be carried out regardless of whether the Tempera-
ture Controller is performing reverse (heating) or normal (cooling)
operation. To stop auto-tuning, hold down the Level Key and Mode
Key again simultaneously for 1 second minimum. All settings will re-
turn to those prior to the beginning of auto-tuning. Automatic tuning
can be executed at any time: at power application, while the temper-
ature is rising, or after the control action has stabilized.
The Temperature Controller is provided with self-diagnostic functions, and will display an error message on the PV display when an error is
detected.
Message
ffff
Cause
Input temperature has exceeded the upper
limit of the temperature range by more than
20%C.
Control output
Normal
Reverse
Open: OFF
Close: ON
Open: ON
Close: OFF
Alarm output
Sends alarm signal in ac-
cordance with the set
alarm mode.
––––
Input temperature has fallen below the lower
limit of the temperature range by more than
20%C.*
Open: ON
Close: OFF
Open: OFF
Close: ON
Sends alarm signal in ac-
cordance with the set
alarm mode.
5.err (flashes)
The thermocouple has burned out or
short-circuit bar has been removed. The plati-
num resistance thermometer has burned out
or A and B terminals have been short-cir-
cuited.
Open: OFF
Close: ON
Open: ON
Close: OFF
Sends alarm signal in ac-
cordance with the set
alarm mode. Proportional
alarm output is OFF, how-
ever.
e111 (flashes)
e333 (flashes)
Memory failure (e111) or A/D converter failure
(e333) has occurred. Temperature Controller
must be repaired if recovery is not made by
turning power off once and on again.
Open: OFF
Close: OFF
Open: OFF
Close: OFF
OFF
*When the temperature resistance thermometer is used, this message is displayed when the temperature has fallen below -99.9%C.
11

11 Page







PáginasTotal 14 Páginas
PDF Descargar[ Datasheet E5AX-P.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
E5AX-PTemperature ControllerOMRON
OMRON

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar